Permit: T08CM01443

Parcel: 106024110


Addresses:

3985 N STONE AV A


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01443

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/18/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/17/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
03/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CORRECTLY COLOR PHASE WATER HEATER DISCONNECT
2. BOX TO BE RATED FOR CEILING FAN AND USE APPROVED HARDWARE
3. GROUND SWITCHES
4. USE PROPER HARDWARE FOR DEVICES AND PLATES
5. TIGHTEN LOOSE FITTINGS
6. WHERE IS BOX AT FRONT & PORCH LIGHTS?
7. FINISH #1, 10, 11, 12 PREVIOUS INSPECTION

*A REFEE MAY BE ASSESSED AS PER ADMIN. CODES
02/19/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" - 314.20
2. USE APPROVED CORD FOR DISHWASHER
3. USE APPROVED CORD FOR HOOD AND CONNECTOR
4. WHERE IS 2ND CIRCUIT SERVING COUNTER TOP - 210.52
5. DISCONNECTING MEANS NEEDED FOR WATER HEATER
6. ONLY ONE CONDUCTOR UNDERGROUND TERMINAL SCREW BATH LIGHT
7. SECURE KITCHEN FIXTURE TO CEILING
8. GROUND FIXTURE
9. PROTECT CONDUCTORS AT FIXTURE
10. LABEL PANEL DIRECTORY AS PER 408.4
11. NEED AN ELECTRIC PLAN
12. NEED ANTI-TIP DEVICE AT RANGE
01/26/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/21/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The grounding electrode conductor is not installed per code.| 220*
1. INSTALL GROUNDING ELECTRODE SYSTEM
PER 250.60, 250.64

*PLEASE HAVE QUALIFIED ELECTRICIAN ON SITE
01/14/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
NO WORK PROGRESS
PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION
12/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) INSTALL ALL STRANDS UNDER LUG AND TIGHTEN CONDUCTOR TERMINATION-TAP BOX
2) PLEASE VERIFY 2ND GROUND ROD
12/09/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANEL
2. FULLY IDENTIFY UNGROUNDED CONDUCTORS
3. GROUNDING ELECTRODE SYSTEM MISSING