Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01443
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/18/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/17/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
03/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CORRECTLY COLOR PHASE WATER HEATER DISCONNECT 2. BOX TO BE RATED FOR CEILING FAN AND USE APPROVED HARDWARE 3. GROUND SWITCHES 4. USE PROPER HARDWARE FOR DEVICES AND PLATES 5. TIGHTEN LOOSE FITTINGS 6. WHERE IS BOX AT FRONT & PORCH LIGHTS? 7. FINISH #1, 10, 11, 12 PREVIOUS INSPECTION *A REFEE MAY BE ASSESSED AS PER ADMIN. CODES |
|
02/19/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" - 314.20 2. USE APPROVED CORD FOR DISHWASHER 3. USE APPROVED CORD FOR HOOD AND CONNECTOR 4. WHERE IS 2ND CIRCUIT SERVING COUNTER TOP - 210.52 5. DISCONNECTING MEANS NEEDED FOR WATER HEATER 6. ONLY ONE CONDUCTOR UNDERGROUND TERMINAL SCREW BATH LIGHT 7. SECURE KITCHEN FIXTURE TO CEILING 8. GROUND FIXTURE 9. PROTECT CONDUCTORS AT FIXTURE 10. LABEL PANEL DIRECTORY AS PER 408.4 11. NEED AN ELECTRIC PLAN 12. NEED ANTI-TIP DEVICE AT RANGE |
|
01/26/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
01/21/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The grounding electrode conductor is not installed per code.| 220* 1. INSTALL GROUNDING ELECTRODE SYSTEM PER 250.60, 250.64 *PLEASE HAVE QUALIFIED ELECTRICIAN ON SITE |
|
01/14/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio NO WORK PROGRESS PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION |
|
12/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL ALL STRANDS UNDER LUG AND TIGHTEN CONDUCTOR TERMINATION-TAP BOX 2) PLEASE VERIFY 2ND GROUND ROD |
|
12/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANEL 2. FULLY IDENTIFY UNGROUNDED CONDUCTORS 3. GROUNDING ELECTRODE SYSTEM MISSING |