Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01436
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/04/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE CAP UNUSED PIN CONNECTOR OPENING 2) OK LABELING-PARTIAL FINAL-SUBJECT TO VERIFICATION OF STRUCTURAL BEING ADDED TO PERMIT |
|
| 02/13/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* HAVE BUILDING INSPECTOR VERIFY FIRESTOPPING RECEIVED COPIES OF GFI AND BREAKER TEST RECEIVED COPIES OF SWITCHBOARD FOR REVIEW |
|
| 12/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* EXTERIOR 1. A GROUNDING ELECTRODE SYSTEM IS NEEDED THERE ARE SEPARATE STRUCTURES 2. IDENTIFY GROUNDING EQUIPMENT CONDUCTORS AT LUGS 3. INSTALL ARC FAULT LABELING 4. SWITCHBOARDS ARE FOR 400A MAX GENERATOR INPUTS NOT FEED FOR TEMP EQUIPMENT -- NEED NRTL RECERTIFICATION IF CHANGED TO OUTPUT 5. NEED COPIES OF GFI TEST 6. NEED PLANS FOR OUTSIDE SWITCHBOARDS 7. HAVE BUILDING INSPECTOR VERIFY FIRE STOPPING |