Permit: T08CM01436

Parcel: 11711076A


Addresses:

126 E ALAMEDA ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01436

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/23/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PLEASE CAP UNUSED PIN CONNECTOR OPENING
2) OK LABELING-PARTIAL FINAL-SUBJECT TO VERIFICATION OF STRUCTURAL BEING ADDED TO PERMIT
02/13/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
HAVE BUILDING INSPECTOR VERIFY FIRESTOPPING
RECEIVED COPIES OF GFI AND BREAKER TEST
RECEIVED COPIES OF SWITCHBOARD FOR REVIEW
12/11/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
EXTERIOR
1. A GROUNDING ELECTRODE SYSTEM IS NEEDED THERE ARE SEPARATE STRUCTURES
2. IDENTIFY GROUNDING EQUIPMENT CONDUCTORS AT LUGS
3. INSTALL ARC FAULT LABELING
4. SWITCHBOARDS ARE FOR 400A MAX GENERATOR
INPUTS NOT FEED FOR TEMP EQUIPMENT --
NEED NRTL RECERTIFICATION IF CHANGED TO OUTPUT
5. NEED COPIES OF GFI TEST
6. NEED PLANS FOR OUTSIDE SWITCHBOARDS
7. HAVE BUILDING INSPECTOR VERIFY FIRE STOPPING