Permit: T08CM01427

Parcel: 105110490

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM01427

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/29/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE ACCESS TO ROOF
10/28/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
10/22/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE BIRD SCREEN AT EXHAUST OUTLETS
2. DATA PLATES ON UNITS IDENTIFIED
3. LABEL RTU's
4. SEE BUILDING INSPECTOR FOR TEMP C OF O
10/21/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BALANCE REPORT NOT WITHIN DESIGN PARAMETERS +/- 10%
10/20/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
RTU-3 DUCT SMOKE DETECTOR FAILED
PROVIDE AIR BALANCE
10/17/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REACH IN BOX CONDENSATE NOT PER PLANS
2. PROVIDE DUCT SMOKE TEST
3. AIR BALANCE REPORT NOT COMPLETE