Permit: T08CM01427

Parcel: 105110490

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM01427

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/03/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/02/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISHED FLOOR
09/10/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNDER SLAB INSPECTED ON DEMO PERMIT
WILL RECHECK FLANGES AFTER FLOOR IS SET
FINISH INSULATING - OK TO COVER WALLS
09/09/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. THREE COMPARTMENT SINK TO BE DIRECTLY CONNECTED TO THE SANITARY SEWER. ONE COMPARTMENT MAY BE INDIRECTLY WASTED IF IT IS A SANITIZING BOWL
(AS REQ'D BY HEALTH DEPT.)
2. PROTECT ABS FROM METAL STUDS
3. INSULATE PIPING PER SPEC.
4. HANG ALL PIPING PER SPEC's
5. ABS WATER TEST OK
09/08/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WHO INSPECTED UNDER SLAB PLUMBING?
PLUMBER NEEDS TO RE-READ P-1, PLUMBING SPEC's, NOTES,
AND SCHEDULES. NOT INSTALLED PER PLAN
HAVE THE PLUMBER COMPLETE SOME SECTION OF WORK
BEFORE CALLING INSPECTION - FAILURE TO DO SO WILL RESULT IN A REINSPECTION FEE