Permit: T08CM01416

Parcel: 12701002C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM01416

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/14/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
UTILIZE CLAMP RING OF FHA DRAIN
06/11/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO COVER WALLS
2. CHECK SINK DRAIN ELEVATIONS
3. VERIFY WH FOR SHOWER, REDLINE CHANGE
4. CALL FOR INSPECTION OF SHOWER PAN LINER
5. SEE UPC INSTALLATION STANDARDS
06/06/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV w/TEST OK
SAFETY PLATES REQUIRED ON CAST IRON
COPPER PIPING WHICH IS PARTIALLY INSTALLED
HAS NOT BEEN DEBURRED
CORRECT ALL COPPER JOINTS
INSTALL PER CODE