Permit: T08CM01383

Parcel: 105102520


Addresses:

4282 N 1ST AV


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T08CM01383

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
11/07/2008 MECHANICAL - HOODS Approved IVRS - Inspection :*
2ND LAYER OF FIRE WRAP IS OK
11/05/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED 1ST LAYER OF FIRE WRAP
OK TO PROCEED WITH 2ND LAYER
10/31/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
OK 1ST LAYER FIRE WRAP
PROVIDE ACCESS DOOR IN GREASE DUCT
PRIOR TO HOOD FINAL
08/28/2008 MECHANICAL - HOODS Cancelled IVRS - RI canceled
08/28/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
GREASE DUCT WELD TEST OK
OK FOR 1ST WRAP
08/27/2008 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*