Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01383
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/07/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* DOCK LEVELER MOTOR HAS BEEN REMOVED LEVELER IS MANUALLY OPERABLE. IF MOTOR IS INSTALLED A LISTED UNIT IS REQUIRED. RECEIVED MONEY ORDER NO. 68241721713 -- $150.00 |
|
01/05/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
01/02/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
12/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PAPERWORK FOR DOCK LEVEL IS NOT A LISTING-NEED 3RD PARTY |
|
12/30/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) STILL WATING ON VERIFICATION OF DOOR LEVER 2) NEED VERIFICATION OF MECHANICAL INSPECTORS CHECK OF HOODS 3) NEED VERIFICATION FROM BLDG INSPECTOR FOR FIRE STOPPING THRU WALL AT RACK ROOM |
|
12/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ROOF 2) OK UPSTAIRS 3) FINISH RACK ROOM |
|
12/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RACK ROOM: 1. PANEL D - SEAL UNUSED CONDUIT 2. FINISH DEVICES 3. DISCONNECTING MEAN W/H MOTOR/PUMP 4. 314.20 AND PLATE BACKROOM: 1. PANEL SCHEDULES 408.4 - DISTINGUISHABLE FROM ONE ANOTHER UPSTAIRS: 1. BOX OVERFILLED 2. MISSING SWITCH PLATES CHECK ROOF NEXT TIME OK SALES FLOOR LIGHTS OK CASH WRAPS AS NOTED LIGHTS FOR CASH WRAP REMOVED - IF ELECTRIFIED WILL NEED TO BE LISTED. |
|
12/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROTECT VDV CABLING FROM SHARP METAL EDGES 2. PANEL DIRECTORIES PER 408.4 -- NO ABBREVIATIONS, AND DISTINGUISHABLE FROM ONE ANOTHER 3. PLEASE VERIFY LISTINGS FOR ALL KITCHEN DELI EQUIPMENT, DOCK LEVELER 4. EXIT/FLOOD TO BE AS PER 700.12(F) OK SALES FLOOR LIGHTING |
|
12/16/2008 | ELECTRIC - FINAL | Partial Approval | OK BOAR'S HEAD CASE, BAKERY FREEZER, BATHROOMS, BOILER, DAIRY COOLER 1. FINISH PREVIOUS MARKED ITEMS |
|
12/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOND BUSHING AT BOILER -- 250.97 2. TIGHTEN LOOSE FITTINGS 3. PROPERLY SECURE STRANDED CONDUCTORS UNDER GROUND SCREWS 4. INSTALL FIXTURE DISCONNECT BATHROOMS -- 410.73 5. SINGLE GANG BOX OR RING FOR ONLY 6 LBS. 6. CASH WRAP FIXTURES TO BE LISTED 7. BOXES OVERFILLED AT CASH WRAP OK OLIVE BAR CASE, C2 CASE, RACK ROOM ELECTRIC |
|
12/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROPERLY GROUND REFRIGERATION CASES ENCLOSURES 2. CANNOT USE SHEETMETAL THREAD SCREWS 250.8 3. FINISH CASES 4. ONLY ONE CONDUCTOR TO A LUG 5. WIRE NUTS OVERFILLED 6. MAINTAIN WORKING CLEARANCES AT RACK DISCONNECT 7. CANNOT TRIM CONDUCTORS 8. CLOSE UNUSED OPENINGS 9. M/C CABLE TO TERMINATE OK BEER COOLER, DAIRY COOLER, COFFEE/PEANUT AISLE, MEAT/DELI CASES, SERVICE MEAT CASES, SPECIAL PRODUCE, FRUITS & VEGETABLES, DAIRY, FROZEN FOODS CASES, MEAT FREEZER & COOLER, PRODUCE COOLER |
|
12/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
12/11/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
12/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK GONDOLAS NORTH OF COLUMN 3.0 OK 400 AMP DISCONNECT AND TRANSFORMER AT CEILING 1. NEED APPROVED STAMP ON TRANSFORMER DETAIL 2. PROVIDE AN EFFECTIVE GROUND FOR TRANSFORMER |