Permit: T08CM01383

Parcel: 105102520


Addresses:

4282 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01383

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/07/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
DOCK LEVELER MOTOR HAS BEEN REMOVED LEVELER IS MANUALLY OPERABLE. IF MOTOR IS INSTALLED A LISTED
UNIT IS REQUIRED.

RECEIVED MONEY ORDER NO. 68241721713 -- $150.00
01/05/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
01/02/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
12/31/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PAPERWORK FOR DOCK LEVEL IS NOT A LISTING-NEED 3RD PARTY
12/30/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) STILL WATING ON VERIFICATION OF DOOR LEVER
2) NEED VERIFICATION OF MECHANICAL INSPECTORS CHECK OF HOODS
3) NEED VERIFICATION FROM BLDG INSPECTOR FOR FIRE STOPPING THRU WALL AT RACK ROOM
12/29/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK ROOF
2) OK UPSTAIRS
3) FINISH RACK ROOM
12/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RACK ROOM:
1. PANEL D - SEAL UNUSED CONDUIT
2. FINISH DEVICES
3. DISCONNECTING MEAN W/H MOTOR/PUMP
4. 314.20 AND PLATE

BACKROOM:
1. PANEL SCHEDULES 408.4 - DISTINGUISHABLE FROM ONE ANOTHER

UPSTAIRS:
1. BOX OVERFILLED
2. MISSING SWITCH PLATES

CHECK ROOF NEXT TIME

OK SALES FLOOR LIGHTS
OK CASH WRAPS AS NOTED

LIGHTS FOR CASH WRAP REMOVED - IF ELECTRIFIED WILL NEED TO BE LISTED.
12/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PROTECT VDV CABLING FROM SHARP METAL EDGES
2. PANEL DIRECTORIES PER 408.4 -- NO ABBREVIATIONS, AND DISTINGUISHABLE FROM ONE ANOTHER
3. PLEASE VERIFY LISTINGS FOR ALL KITCHEN DELI EQUIPMENT, DOCK LEVELER
4. EXIT/FLOOD TO BE AS PER 700.12(F)

OK SALES FLOOR LIGHTING
12/16/2008 ELECTRIC - FINAL Partial Approval OK BOAR'S HEAD CASE, BAKERY FREEZER, BATHROOMS, BOILER, DAIRY COOLER

1. FINISH PREVIOUS MARKED ITEMS
12/16/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOND BUSHING AT BOILER -- 250.97
2. TIGHTEN LOOSE FITTINGS
3. PROPERLY SECURE STRANDED CONDUCTORS UNDER GROUND SCREWS
4. INSTALL FIXTURE DISCONNECT BATHROOMS -- 410.73
5. SINGLE GANG BOX OR RING FOR ONLY 6 LBS.
6. CASH WRAP FIXTURES TO BE LISTED
7. BOXES OVERFILLED AT CASH WRAP

OK OLIVE BAR CASE, C2 CASE, RACK ROOM ELECTRIC
12/15/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PROPERLY GROUND REFRIGERATION CASES ENCLOSURES
2. CANNOT USE SHEETMETAL THREAD SCREWS 250.8
3. FINISH CASES
4. ONLY ONE CONDUCTOR TO A LUG
5. WIRE NUTS OVERFILLED
6. MAINTAIN WORKING CLEARANCES AT RACK DISCONNECT
7. CANNOT TRIM CONDUCTORS
8. CLOSE UNUSED OPENINGS
9. M/C CABLE TO TERMINATE

OK BEER COOLER, DAIRY COOLER, COFFEE/PEANUT AISLE,
MEAT/DELI CASES, SERVICE MEAT CASES, SPECIAL PRODUCE,
FRUITS & VEGETABLES, DAIRY, FROZEN FOODS CASES,
MEAT FREEZER & COOLER, PRODUCE COOLER
12/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/11/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
12/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK GONDOLAS NORTH OF COLUMN 3.0
OK 400 AMP DISCONNECT AND TRANSFORMER AT CEILING

1. NEED APPROVED STAMP ON TRANSFORMER DETAIL
2. PROVIDE AN EFFECTIVE GROUND FOR TRANSFORMER