Permit: T08CM01383

Parcel: 105102520


Addresses:

4282 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01383

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. M/C CABLE TO TERMINATE
2. BOXES OVERFILLED
3. AT TAP BOX WIRE BENDING RADIUS
4. FINISH PREVIOUS MARKED ITEMS

OK TO LUGS PANELS -- "A", "B", "C"
OK "SDP" TO ENERGIZE
OK TO TILE KITCHEN/DELI EXCEPT AS NOTED
OK TO TILE CASH OFFICE
12/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ENERGIZE PANEL "HIA"

1. 3/0 CONDUCTORS IN 1/0 - 14 LUGS
2. FINISH #3 & 6 FROM 12/2/08 AS DISCUSSED
3. FINISH 3, 4, 7 FROM 12/3/08
4. FINISH REFER RACK -- UNUSED OPENINGS
12/03/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT FIRE ALARM FLEX -- 300.11
2. SEAL UNUSED CONDUIT OPENING ABOVE PANELS
3. SEAL ABOVE WALK-IN BOXES PER 300.7
4. USE TERMINAL END WITH STRANDED CONDUCTOR
5. MAKE UP & CLOSE JUNCTION BOX ABOVE HOOD
6. VERIFY DERATING OF CONDUCTORS PER 310.15
7. USE APPROVED PARTS FOR RE-LOCK SYSTEM
8. FINISH #2 , 3 AND 6 -- PREVIOUS INSPECTION

A REFEE MAY BE ASSESSED FOR WORK NOT PROGRESSING
12/02/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOND BUSHINGS PER 250.97
2. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANELS
3. INSTALL GROUNDING ELECTRODE CONDUCTOR PER 250.64
4. INSTALL DISCONNECT FOR LUMINARIES AS PER 410.73(G)
5. CONDUIT SUPPORT TO SUPPORT CONDUIT
6. EMT CANNOT SUPPORT LIGHTS AND PREVENT MOVEMENT
7. ATTACH FIXTURES SECURELY TO GRID 410.16
8. FIXTURE SUPPORT WIRES TO BE OPPOSITE CORNERS
9. SUPPORT ELECTRIC PER 300.11
11/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. EMT NOT ALLOWED TO SUPPORT LIGHTS

OK THE REST OF 2ND FLOOR
11/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NO MORE THAN 360 DEG. IN CONDUIT RUNS

OK HARD LID BATHROOM VESTIBULE

2ND FLOOR:
1. GUTTER TO BE ACCESSIBLE
2. EXTEND CONDUIT OUT OF WALL AND FILL UNUSED OPENINGS
3. USE CORRECT FITTINGS WITH FLEX

*MOST CONDUITS UP OUT OF WALLS HAVE 270 DEG. SO FAR

OK OFFICE MGR, DEPT MGR., SCAN AND I.T. WALLS
11/12/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK BATHROOM LIDS ONLY
11/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. TIGHTEN LOOSE FITTINGS

OK LADIES RESTROOM WALLS AFTER CORRECTIONS
10/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PRODUCE PREP, BACKSTOCK, MENS, NORTH HALL
WALLS ONLY

MENS HARD LID ONLY
10/21/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SUPPORT CONDUITS IN WALLS AS PER CODE

DO NOT HANG DRYWALL UNTIL APPROVED
09/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOMS #DELI/MEATS, CUT RM, CASH OFFICE

DO NOT ONE SIDE UNTIL CLEARED