Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM01383
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. M/C CABLE TO TERMINATE 2. BOXES OVERFILLED 3. AT TAP BOX WIRE BENDING RADIUS 4. FINISH PREVIOUS MARKED ITEMS OK TO LUGS PANELS -- "A", "B", "C" OK "SDP" TO ENERGIZE OK TO TILE KITCHEN/DELI EXCEPT AS NOTED OK TO TILE CASH OFFICE |
|
12/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE PANEL "HIA" 1. 3/0 CONDUCTORS IN 1/0 - 14 LUGS 2. FINISH #3 & 6 FROM 12/2/08 AS DISCUSSED 3. FINISH 3, 4, 7 FROM 12/3/08 4. FINISH REFER RACK -- UNUSED OPENINGS |
|
12/03/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT FIRE ALARM FLEX -- 300.11 2. SEAL UNUSED CONDUIT OPENING ABOVE PANELS 3. SEAL ABOVE WALK-IN BOXES PER 300.7 4. USE TERMINAL END WITH STRANDED CONDUCTOR 5. MAKE UP & CLOSE JUNCTION BOX ABOVE HOOD 6. VERIFY DERATING OF CONDUCTORS PER 310.15 7. USE APPROVED PARTS FOR RE-LOCK SYSTEM 8. FINISH #2 , 3 AND 6 -- PREVIOUS INSPECTION A REFEE MAY BE ASSESSED FOR WORK NOT PROGRESSING |
|
12/02/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND BUSHINGS PER 250.97 2. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANELS 3. INSTALL GROUNDING ELECTRODE CONDUCTOR PER 250.64 4. INSTALL DISCONNECT FOR LUMINARIES AS PER 410.73(G) 5. CONDUIT SUPPORT TO SUPPORT CONDUIT 6. EMT CANNOT SUPPORT LIGHTS AND PREVENT MOVEMENT 7. ATTACH FIXTURES SECURELY TO GRID 410.16 8. FIXTURE SUPPORT WIRES TO BE OPPOSITE CORNERS 9. SUPPORT ELECTRIC PER 300.11 |
|
11/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. EMT NOT ALLOWED TO SUPPORT LIGHTS OK THE REST OF 2ND FLOOR |
|
11/20/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NO MORE THAN 360 DEG. IN CONDUIT RUNS OK HARD LID BATHROOM VESTIBULE 2ND FLOOR: 1. GUTTER TO BE ACCESSIBLE 2. EXTEND CONDUIT OUT OF WALL AND FILL UNUSED OPENINGS 3. USE CORRECT FITTINGS WITH FLEX *MOST CONDUITS UP OUT OF WALLS HAVE 270 DEG. SO FAR OK OFFICE MGR, DEPT MGR., SCAN AND I.T. WALLS |
|
11/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BATHROOM LIDS ONLY |
|
11/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. TIGHTEN LOOSE FITTINGS OK LADIES RESTROOM WALLS AFTER CORRECTIONS |
|
10/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PRODUCE PREP, BACKSTOCK, MENS, NORTH HALL WALLS ONLY MENS HARD LID ONLY |
|
10/21/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SUPPORT CONDUITS IN WALLS AS PER CODE DO NOT HANG DRYWALL UNTIL APPROVED |
|
09/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROOMS #DELI/MEATS, CUT RM, CASH OFFICE DO NOT ONE SIDE UNTIL CLEARED |