Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08CM01381

Parcel: 105102520


Addresses:

4262 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01381

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/25/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) LABEL DISC. AT SERVICE FOR PANEL SERVED-NOT JUST THE SITE ADDRESS
2) GROUND X-FORMER PER 250.30 NCE
3) CONTR. NOT ON SITE
08/19/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) POST BOND
08/14/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SEE NOTES 4246
06/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BONDING FOR WATER, GAS, BLDG STEEL SIZED PER 250.104-250.66
2) POST BOND FOR TEMP POWER
03/11/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK BOXES AND CONDUITS
FRONT AND BACK WALLS