Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/23/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FINISH #1 & #2 OF PREVIOUS INSPECTION OK TO TILE AFTER CORRECTIONS |
|
| 05/20/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL UNUSED OPENINGS IN BOXES 2. REMOVE ABANDONED LOW VOLTAGE WIRING 3. FINISH DATA WIRING - SUPPORT TO STRUCTURE - NOT TO CEILING GRID OR OTHER EQUIPMENT 4. SECURE ALL FIXTURES TO GRID 5. REMOVE UNUSED RACEWAYS OR SEAL OFF PARTIAL INSPECTION ONLY - ELECTRICIAN TO GO THROUGH CEILING AND MAKE SURE ALL PER CODE -- TILES INSTALLED BEFORE APPROVAL |
|
| 05/19/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT LOCKED. NO ACCESS TO UNIT. |
|
| 05/08/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |