Permit: T08CM01370

Parcel: 133148070


Addresses:

1580 N KOLB RD #100

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/28/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/23/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
FINISH #1 & #2 OF PREVIOUS INSPECTION

OK TO TILE AFTER CORRECTIONS
05/20/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL UNUSED OPENINGS IN BOXES
2. REMOVE ABANDONED LOW VOLTAGE WIRING
3. FINISH DATA WIRING - SUPPORT TO STRUCTURE - NOT TO CEILING GRID OR OTHER EQUIPMENT
4. SECURE ALL FIXTURES TO GRID
5. REMOVE UNUSED RACEWAYS OR SEAL OFF

PARTIAL INSPECTION ONLY - ELECTRICIAN TO GO THROUGH CEILING AND MAKE SURE ALL PER CODE -- TILES INSTALLED BEFORE APPROVAL
05/19/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
UNIT LOCKED.
NO ACCESS TO UNIT.
05/08/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*