Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
| 05/08/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROTECT FLEX AT TOP PLATE 2. SUPPORT VDV CABLING IN WALLS 725.24 3. PROTECT VDV CABLING FROM SHARP METAL EDGES TOP PLATE & FLEX 4. SUPPORT M/C CABLES 6' INTERVALS 5. SUPPORT BOXES AND CONDUITS ABOVE CEILING 6. FILL UNUSED OPENINGS IN BOXES AND CONDUITS 7. PROVIDE LETTER AUTHORIZING USE OF M/C CABLE 8. PLEASE PROVIDE BOX SUPPORTS 9. 725.3 & 29, 800.3 & 24, 300.11 WILL APPLY ABOVE CEILINGS 10. RELOCATED LIGHTS TO BE ATTACHED TO GRID DO NOT ONE SIDE WITHOUT ELECTRICAL CLEARANCES |