Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2011 | FIRE - FINAL | Approved | PER SIGNED JOB CARD | |
| 03/31/2011 | FIRE - FINAL | Denied | Not approved 3/31/11 1.) Need to test Fire Alarm system. 2.) Need annual Fire Alarm inspection. 3.) Need plans and permit for Alarm System |
|
| 02/24/2011 | FIRE - FINAL | Not ready for Inspection | Not ready for inspection 2/23/11 1.) Fire Alarm System has been disconnected. Must be reconnected in order to monitor water flow and tamper valve. 2.) Need plans and permit for installation of the newly added duct detectors. DT's must be connected to and monitored on the panel. 3.) Need back-up battery for Fire Alarm Panel. 4.) Need smoke detector over Fire Alarm Panel. 5.) Need annual Fire Alarm inspection report. 6.) Need illuminated Exit sign for SW door, east wall. 7.) Need to complete life/safety inspection |