Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08CM01363

Parcel: 10703143A


Addresses:

2565 N HUACHUCA DR

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/18/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
OK TO COVER
11/17/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. VERTICAL BY HORIZONTAL CHANGE OF DIRECTION
TO BE A SWEEP
2. CLEANOUTS SHALL OPEN IN THE DIRECTION OF FLOW
11/13/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection 1. WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN, IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE, DOWNSTREAM OF THE TRAP BEING SERVED.
2. ABS TO BE LAID ON A FIRM BED, NO BRIDGING ALLOWED
3. FURNCO NOT PERMITTED UNDER THE BUILDING
4. VERTICAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP
5. ALL PIPING BELOW SLAB TO HAVE 2% FALL
UPPER TERMINAL C.O. TO BE FULL SIZE
3" BRANCH PIPING TO HAVE FULL SIZE CLEANOUT
TEST ALL DWV PIPING TO TEN FEET