Permit: T08CM01355

Parcel: 13219049E


Addresses:

2833 E MISSOURI ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/08/2008 FRAMING Approved IVRS - Inspection :*
12/05/2008 FRAMING Not ready for Inspection IVRS - Inspection :*
12/04/2008 FRAMING Not ready for Inspection IVRS - Inspection :*
1) STUDS 2 X 4 AT GARAGE BATHROOM WALL OVER DRILLED, RUN RE-VENT UP TO CEILING TIE IN, SISTER STUDS TO DRILLED STUDS
2) NEED DWV TEST
3) KIT 2ND SINK VENT TO BE 6" ABOVE FLOOD RIM BEFORE GOING HORIZONTAL, OR INSTALL AIR ADMITTANCE VALVE
4) FINISH FIREPLACE FIRE STOP AT CEILING, GAS LINE AT F.P. GAS VALVE TO HAVE A KEY SHUT OFF, NEED 1/2 DIAMETER PENETRATION INTO FIRE BOX
5) 50 AMP CIRCUIT KIT N/M WIRE 60 DEGREE ONLY GOOD FOR 40 AMP SEE HAND OUT
6) QUESTION TRUSS CO. HOW MUCH TOLERENCE AT BEARING END INTERIOR VERT WLB NOT ON TOP OF BEARING WALL
7) WINDOWS NOT INSTALLED