Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/29/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* THIS SYSTEM HAS HOT WATER RECIRCULATION AND THE CHECK VALVE ON THE COLD INLET HAS BEEN REMOVED SEPARATING HOT RETURN FROM COLD SUPPLY, PLEASE PROVIDE A PLAN TO ROBERT SHERRY FOR PLAN REVISION AT 201 N STONE |
|
| 07/25/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. THIS SYSTEM HAS A CHECK VALVE ON COLD WATER INLET TO WATER HEATER AND WOULD REQUIRE A PROPERLY SIZED EXPANSION TANK 2. PLEASE VERIFY WITH MANUFACTURER 1/2" PIPING IS CORRECT BETWEEN EXCHANGER AND STORAGE TANK 3. PLEASE VERIFY DE-IONIZED WATER IS CORRECT PER MANUFACTURER FOR TRANSFER FLUID 4. CORRECT DAMAGED FLEX PIPING TO STORAGE TANK |