Permit: T08CM01327

Parcel: 11606001G

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/04/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
07/29/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
THIS SYSTEM HAS HOT WATER RECIRCULATION AND THE CHECK VALVE ON THE COLD INLET HAS BEEN REMOVED SEPARATING HOT RETURN FROM COLD SUPPLY, PLEASE PROVIDE A PLAN TO ROBERT SHERRY FOR PLAN REVISION
AT 201 N STONE
07/25/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. THIS SYSTEM HAS A CHECK VALVE ON COLD WATER INLET TO WATER HEATER AND WOULD REQUIRE A PROPERLY SIZED EXPANSION TANK
2. PLEASE VERIFY WITH MANUFACTURER 1/2" PIPING IS CORRECT BETWEEN EXCHANGER AND STORAGE TANK
3. PLEASE VERIFY DE-IONIZED WATER IS CORRECT PER MANUFACTURER FOR TRANSFER FLUID
4. CORRECT DAMAGED FLEX PIPING TO STORAGE TANK