Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GROUNDING ELECTRODE BOND TO BE AS PER 250.64 2. LABEL BREAKERS PER 408.4 3. ONLY ONE CONDUCTOR PER LUG |
|
| 06/19/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSTALLATION NOT FINISHED DISCONNECTS NOT GROUPED? |
|
| 06/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED PLANS ON SITE & GARAGE ACCESS |