Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM01320
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/07/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1 COMPLETE POWER POLE CONNECTIONS |
|
11/06/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL SEISMIC WIRES ON 2X4 GRID FIXTURES 2. FLUORESCENT FIXTURES TO COMPLY WITH 410.73 NEC (G) FOR DISCONNECTING MEANS FOR BALLASTS |
|
10/20/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/17/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK MAIN SALES FLOOR 2. EM. LTG. TO COMPLY WITH 700.16 |