Permit: T08CM01315

Parcel: 112063200


Addresses:

2110 E WATER ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/13/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING -- 250.8
2. DISCONNECT SWITCH ON EAST SIDE RATE 15A ON 20A CIRCUIT
3. FINISH #2 PREVIOUS INSPECTION
09/16/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. A DISCONNECTING MEANS IS NEEDED - EAST UNIT
2. LABEL BREAKERS PER 408.4 - BOTH PANELS
3. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANEL
4. MAINTAIN WORKING CLEARANCES AT NEW BREAKERS

OK TO COVER TRENCH