Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING -- 250.8 2. DISCONNECT SWITCH ON EAST SIDE RATE 15A ON 20A CIRCUIT 3. FINISH #2 PREVIOUS INSPECTION |
|
| 09/16/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. A DISCONNECTING MEANS IS NEEDED - EAST UNIT 2. LABEL BREAKERS PER 408.4 - BOTH PANELS 3. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANEL 4. MAINTAIN WORKING CLEARANCES AT NEW BREAKERS OK TO COVER TRENCH |