Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T08CM01299
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2008 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 07/11/2008 | FIRE SPKLR - OH PIPING & HYDRO | Not ready for Inspection | 1ST correct sprinkler uprights in multipurpose room by duck work 2nd Floor get insulation off all sprinkler heads 2nd floor exit eastside hallway add drop for proper coverage. |
|
| 06/02/2008 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 200 psi for 2 hours OK 1ST FL Add sprinkler coverage in storage room at inspectors test valve. 1st FL correct upright sprinkler coverage by beam and A/C blowers 1st FL Correct upright coverage in classroom southwest corner. 2nd FL in communications room check to see if there is going to be a ceiling in that room if so need to add coverage. |