Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2009 | ELECTRIC - FINAL | Approved | OK PER CHANGES TO LISTING AND IECC CALC'S OK PER RICK HOLLANDER |
|
| 08/28/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/28/2009 | ELECTRIC - FINAL | Partial Approval | FINAL SUBJECT TO IECC REVISION APPROVAL | |
| 08/17/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FIXTURES TO HAVE DISCONNECTS PER 410.73 2) USE APPROVED PARTS WITH FLOOR BOXES 3) EM AND EXIT LIGHTS TO BE PER 700.12 (F) 4) FIXTURES NOT PER PLANS OR ECC LIGHTING CALCULATIONS 5) SIGN CIRCUIT TO BE PER 600.5 6) VDV BOX TO BE FLUSH IN COMBUSTIBLES 314.20 |