Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM01278
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/15/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/06/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MAINTAIN WORKING CLEARANCES AT METER 110.26 2) CONDUCTORS IN GUTTER TO BE PER 230.7 3) VERIFY GROUNDING ELECTRODE SYSTEM 4) CONDUCTORS LARGER THAN #8 TO BE STRANDED 5) LABEL EQUIPMENT 6) INSTALL REJECTION PINS 7) NO SERVICE CONDUCTORS INSTALLED |
|
06/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS AND LIDS AS PER REVISED PLANS |
|
03/31/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* *314.20 WILL APPLY OK FLOOR BOXES & PVC CONDUITS 1. SUPPORT M/C WITHIN 12" OF PANEL 2. PROTECT M/C CABLE IN SHALLOW STUD WALLS 3. NEED REVISED PLANS FOR NEW RECEPTACLES & CIRCUITS 4. PLEASE PROVIDE A LETTER AUTHORIZING M/C CABLE OK WALL SUBJECT TO LETTERS |