Permit: T08CM01278

Parcel: 12902091D


Addresses:

184 S STRATFORD DR

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/28/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/15/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/06/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) MAINTAIN WORKING CLEARANCES AT METER 110.26
2) CONDUCTORS IN GUTTER TO BE PER 230.7
3) VERIFY GROUNDING ELECTRODE SYSTEM
4) CONDUCTORS LARGER THAN #8 TO BE STRANDED
5) LABEL EQUIPMENT
6) INSTALL REJECTION PINS
7) NO SERVICE CONDUCTORS INSTALLED
06/22/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS AND LIDS AS PER REVISED PLANS
03/31/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
*314.20 WILL APPLY
OK FLOOR BOXES & PVC CONDUITS

1. SUPPORT M/C WITHIN 12" OF PANEL
2. PROTECT M/C CABLE IN SHALLOW STUD WALLS
3. NEED REVISED PLANS FOR NEW RECEPTACLES & CIRCUITS
4. PLEASE PROVIDE A LETTER AUTHORIZING M/C CABLE

OK WALL SUBJECT TO LETTERS