Permit: T08CM01277

Parcel: 141185500


Addresses:

9417 E OLD VAIL RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/23/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
01/26/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CLEANOUT COVERS IN SIDEWALK THAT ARE APPROVED FOR THAT APPLICATION AND DO NOT CREATE A TRIPPING HAZARD.
2. COMMERCIAL BUILDINGS REQUIRE OPEN FRONT SEATS
ON STOOLS (TOILETS)
3. NOTE: FLUSH HANDLE TO BE TO OPEN SIDE OF RESTROOM ON TOILETS IN ADA FACILITIES
4. PROVIDE CHLORINE & BACTERIA REPORT FOR STERILIZATION OF BUILDING POTABLE WATER SYSTEM
5. VERIFY A FLASHING FOR ROOF PENETRATION OF VENT
PIPE AND PAINT EXPOSED ABS VENT PIPE TO PROTECT
FROM SUN DAMAGE
6. BACK WATER VALVE TO BE ACCESSIBLE FROM SURFACE AND ACCESS TERMINATED CORRECTLY.