Permit: T08CM01277

Parcel: 141185500


Addresses:

9417 E OLD VAIL RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/23/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BOX EXTENSIONS ON SWITCHES IN TILE BOXES MORE THAN 1/4" BACK
2. MC CABLE TO CAR LIFT TO BE PROTECTED FROM PHYSICAL DAMAGE
3. DO NOT SEE LISTING MARKING OR MARK ON LIFT TO BE CERTIFIED AUTO LIFT
4. FINISH INSTALLING AIR COMPRESSOR. CANNOT BE EXPOSED TO RAIN
5. NL TO BE ON 24/7
6. NEED BREAKER LOCK FOR EM/NL CIRCUIT
7. NUMBER BREAKERS IN PANEL
8. REVISE PLANS FOR HAZARDOUS
LOCATIONS @ CEILING/ROOF AREA
12/23/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED REJECTION PINS IN SERVICE DISCONNECT FOR FUSES
2) FINAL INSPECTION TO BE DONE AFTER POWER TURNED ON