Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BOX EXTENSIONS ON SWITCHES IN TILE BOXES MORE THAN 1/4" BACK 2. MC CABLE TO CAR LIFT TO BE PROTECTED FROM PHYSICAL DAMAGE 3. DO NOT SEE LISTING MARKING OR MARK ON LIFT TO BE CERTIFIED AUTO LIFT 4. FINISH INSTALLING AIR COMPRESSOR. CANNOT BE EXPOSED TO RAIN 5. NL TO BE ON 24/7 6. NEED BREAKER LOCK FOR EM/NL CIRCUIT 7. NUMBER BREAKERS IN PANEL 8. REVISE PLANS FOR HAZARDOUS LOCATIONS @ CEILING/ROOF AREA |
|
| 12/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED REJECTION PINS IN SERVICE DISCONNECT FOR FUSES 2) FINAL INSPECTION TO BE DONE AFTER POWER TURNED ON |