Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS RESTROOMS 2. OK HARD LIDS RESTROOMS 3. NEED TO POST BOND FOR POWER 4. INSTALL SECONDARY CONDUCTORS FROM XFMR TO CT CAN 5. BOND BUILDING STEEL 6. INSTALL FUSES 7. MARK "SERVICE DISCONNECT" 8. BONDING JUMPERS TO BE SIZED PROPERLY 9. BOND CT ENCLOSURE 10. OK 2 - 2 1/2" FROM SES TO TEP XFMR INSTALL WARNING RIBBON PER NEC 300.5 11. OK WATER BOND |