Permit: T08CM01260

Parcel: 10511061R

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM01260

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2008 MECHANICAL - FINAL Approved
11/05/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE AIR BALANCE REPORT
2. PROVIDE DUCT SMOKE DETECTOR TEST
3. COMPLETE ACCESS TO FIRE DAMPERS

NOTE: DUCT SMOKE DETECTOR MUST BE TIED TO MALL ALARM SYSTEM, VERIFY ACTIVATION