Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01260
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/05/2008 | ELECTRIC - FINAL | Partial Approval | OK 1 & 2 PREVIOUS INSPECTION WILL CHECK POWER CONNECTION AT LATER DATE |
|
10/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INTERIOR SIGNS TO BE LISTED 600.3 2. CORDS NOT ALLOWED 400.7 & 8 3. NEED TO SEE CONNECTION TO SERVICE |
|
10/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE AND NOT FLUSH IN COMBUSTIBLES -- 514.20, 314.21 2. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 400.8 3. PROTECT CONDUCTORS FROM SHARP METAL EDGES 4. PANEL DIRECTORIES TO BE AS PER 408.4 |