Permit: T08CM01220

Parcel: 126060470


Addresses:

940 N LONGFELLOW AV

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/05/2010 FRAMING Approved IVRS - Inspection :*
09/29/2010 FRAMING Denied
09/28/2010 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUBMIT AS BUILT AIR ADMITTANCE VALVE IN LIEU OF 2" VTR BATH LAV OR BUILD TO PLAN. CHANGE FROM 2 TO 1 ?
2) SECURE ALL ROMEX 8" FROM BOXES
3) NAIL PROTECT PLUMBING
09/22/2010 FRAMING Denied 1) PVC FITTINGS AND PIPING AT WATER HEATED SUPPLY NOT ALLOWED IN WALLS
2) INSTALL AB'S AT SOLE PLATE PER PLAN/CODE
09/17/2010 FRAMING Denied 1) NAIL PROTECTION NEEDED ON WIRES
2) BOX VERIFIED NOT TO BE OVERLOADED
3) VACUUM BREAKER NEEDED AT EXT. HOSE BIB
4) MINIMUM CLEARANCE NEEDED ON PEX PIPING TO RECESSED LIGHT
5) NAIL PROTECT PEX IN FIRRED OUT BLOCK WALL
6) NAIL PROTECT WALL BEHIND STOOL
08/03/2010 FRAMING Partial Approval IVRS - Inspection :*

1) INTERIOR WALLS