Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01216
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REVISE PERMANENT PANEL DIRECTORY SO IT IS CORRECT AND LEGIBLE 2. MULTI-WIRE (BRANCH CKT WITH SHARED NEUTRAL) TO WASHER RECEPTACLES TO TERMINATE ON SEPARATE PHASES 3. MULTI-WIRE CKT TO SINGLE DEVICE YOKE REQUIRES A 2-POLE BREAKER 4. PIGTAIL NEUTRALS TO SPLIT-WIRED WASHER RECEPTACLE |