Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REVISE PERMANENT PANEL DIRECTORY SO IT IS CORRECT AND LEGIBLE 2. MULTI-WIRE (BRANCH CKT WITH SHARED NEUTRAL) TO WASHER RECEPTACLES TO TERMINATE ON SEPARATE PHASES 3. MULTI-WIRE CKT TO SINGLE DEVICE YOKE REQUIRES A 2-POLE BREAKER 4. PIGTAIL NEUTRALS TO SPLIT-WIRED WASHER RECEPTACLE |