Permit: T08CM01211

Parcel: 115070750


Addresses:

1742 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01211

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2010 ELECTRIC - INTERMEDIATE Approved
04/07/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CANNOT RELEASE POWER TO BUILDING DUE TO HAZARDOUS & UNSAFE CONDITIONS IN UNITS 98-43 + 47-51.
UNITS NOT MATCH WB PERMIT NUMBERS FOR AREAS WORK ON.
03/31/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) UNITS NOT IN CONTRACT ARE IN UNSAFE CONDITIONS
2) MEET WITH FRANK SCHUSTER THE ENGINEER TO DISCUSS JOB FOR PLANS AS ASKED FOR
10/09/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/07/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
LETTER DOES NOT SHOW CIRCUITS, LOADS OR PANEL SCHEDULES NOR DO PLANS
10/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS SUBJECT TO PLANS APPROVAL
UNITS 36-39, 44-47
10/27/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/23/2008 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
10/22/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/14/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES OVERFILLED
2. CIRCUITS TO BE AS PER 210
3. GROUND BOXES WITH GROUND PLATES
4. PROTECT NM CABLES AT STUDS
5. FINISH WALL FURR OUT
6. SUPPORT NM CABLES 8-12" OF BOXES
7. HAVE BUILDING INSPECTOR VERIFY JOIST INTEGRITY
8. PLEASE PROVIDE PANEL SCHEDULES WITH
LOADS & CIRCUITS
09/12/2008 ELECTRIC - INTERMEDIATE Cancelled CANCELLED PER ALEX OF HAR BRO WEST INC. #480-773-2297
09/12/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED PER JOANN
09/09/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
HAVE APPROVED PLANS ON SITE