Permit: T08CM01201

Parcel: 12810064C


Addresses:

5411 E WILLIAMS BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01201

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
NEED TO CHARGE BARKER MORRISSEY FOR 3 HRS. FOR SATURDAY INSPECTION FROM APA ACCOUNT
7:30 AM TO 10:30 AM (BRIAN TOMAKZEWSKI)
03/27/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/16/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/13/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. POST SIGN ON SERVICE FOR GENERATOR ON SITE
2. GROUND AC DISCONNECTS
3. EXITS AND EMS NOT WORKING
4. SEAL OPEN KNOCKOUTS IN GUTTERS
5. INSTALL LOCKNUTS ON MC CONNECTORS
6. ENSURE ALL MC CONNECTORS ARE CONNECTED PROPERLY TO GUTTERS
03/06/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CHECK WITH BUILDING INSPECTOR FOR EXTENSION OF TCO
10/31/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1ST FLOOR
1. ONE EM LIGHT ON GEN. CKT. NOT WORKING
2. SEAL OPEN KNOCKOUTS ELECTRIC ROOM
3. CHECK WITH BUILDING INSPECTOR FOR TCO 1ST FLOOR
I HAVE NO ISSUES
4. CHECK ON HANDLE TIES FOR WORK STATIONS
10/30/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ELECTRICAL CONTRACTOR NOT ON SITE FOR INSPECTION
RECALL WHEN READY
10/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FINAL 2ND FLOOR LAB #234
10/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
THIS WAS AFTER HRS. INSP. ON 10/25/08
NEED TO CHARGE BARKER MORRISSEY FOR 3 HRS.
FOR SATURDAY INSPECTION

2ND FLOOR:
1. NUMEROUS FURNITURE RECEPT. WITH NO POWER
FURNITURE VENDOR TO FIX
2. CHECK WITH BUILDING INSPECTOR FOR EM. LIGHTING REQUIREMENTS IN STAIRWELLS
3. OK EM & EXIT LIGHTS 2ND FLOOR
4. CHECK WITH BUILDING INSPECTOR FOR TCO 2ND FLOOR NO ONE TO OCCUPY 1ST FLOOR
5. NEED TO HAVE GENERATOR LOAD TESTED AND MAINTENANCE DONE TO GET COMPLETE FINAL
10/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
2ND FLOOR
1. MISSING RECEPTACLES, PLATES
2. NUMEROUS FURNITURE RECEPTACLES WITH NO POWER
3. LIGHT FIXTURES NOT WORKING
4. RECEPTACLES WITH NO POWER
5. INSTALL ARCH FLASH WARNING, LABELS @ PANELS
6. CHECK EM LIGHTING WORKING & WIRED PER PLAN
7. MISSING DIRECTIONAL ARROWS ON EXITS
10/20/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1ST FLOOR
1. NUMEROUS FURNITURE RECEPTACLES WITH NO POWER
2. SOME OFFICE RECEPTACLES NO POWER
3. INSTALL EXTENSIONS ON BOXES MORE THAN 1/4" BACK
4. HAVE PANEL COVERS REMOVED
5. CHECK EM LIGHTS. WILL CHECK NEXT INSPECTION.
6. NOT A COMPLETE INSPECTION OF 1ST FLOOR
10/16/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. OK CEILINGS RM. 134 & 234
2. CHECK WITH BUILDING INSPECTOR FOR PERMISSION TO STOCK. I HAVE NO ISSUES. NEED TO ALLOW MIN. OF 3 DAYS FOR FINAL INSPECTIONS.