Permit: T08CM01201

Parcel: 12810064C


Addresses:

5411 E WILLIAMS BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01201

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/30/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/27/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/16/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/13/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/06/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ENSURE MDV GROUNDS AND NEUTRALS SEPARATE
2. GEC TO TERMINATE @ NEUTRAL OR BONDING JUMPER IN XFMR
3. BONDING JUMPERS TO BE SIZED PROPERLY @ DS2
4. BONDING JUMPER FROM XFMR TO DISCONNECT TO BE SIZED PROPERLY
5. SEAL OPEN KNOCKOUTS
6. OK MAKE UP @ SES
10/14/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ED @ 289-0328 - $150.00 CK#1432

1. RECEIVED GFI MAIN TEST & LETTER OF TORQUE
2. ONLY AUTHORIZED PERSONNEL TO HAVE ACCESS TO ELECTRICAL EQUIPMENT

KATHY @ TEP 918-8271/904-5771

CALLED CLEARANCE INTO TEP, MIKE KEISER
10/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PANEL WALLS RM 241
08/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS RMS. 108, 208
2. INSTALL BOX DIVIDERS AT SWITCH LOCATIONS AS NEEDED
08/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS. 133, 110-115, 129, 232
08/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 101-107, 141-144, 135-139, 118-125, 110-115, 201-207
08/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS 2ND FLOOR ROOMS 226-229, 218-222, 237-240, 210-215 AND 233-236
07/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK AREA UNDER RAISED FLOOR OPEN AREAS
1ST & 2ND FLOOR
- SEPARATE HOME RUNS TO NO MORE THAN 7 PER BUNDLE
- BE AWARE OF HANDLE TIE REQUIREMENTS FOR OFFICE FURNITURE NEC 605.6 & 605.7