Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01189
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/20/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER SHAWN |
|
08/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 1" AIR GAP, H20 SOFTNER, DISCHARGE AT WASHER BOX 2) CLEAN UP WIRE CONNECTIONS AT A/C DISCONNECT 3) DON'T INSTALL FLEX LINES 4) FINISH H20 HTR INSTALL AND ROOF SOLAR-ALL OTHERS OK 5) A/C CIRCUIT #6 AL. SE CABLE GOOD FOR 40 AMPS AT 60 DEGREE TABLE MIN CIRCUIT AMPS 33.5 MAX OVER CURRENT 50 AMPS. NEED 40 AMP BREAKER, 40 AMP FUSE, SEE TABLE LEFT WITH PAPERWORK |