Permit: T08CM01189

Parcel: 141386800

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01189

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/20/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER SHAWN
08/19/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1" AIR GAP, H20 SOFTNER, DISCHARGE AT WASHER BOX
2) CLEAN UP WIRE CONNECTIONS AT A/C DISCONNECT
3) DON'T INSTALL FLEX LINES
4) FINISH H20 HTR INSTALL AND ROOF SOLAR-ALL OTHERS OK
5) A/C CIRCUIT #6 AL. SE CABLE GOOD FOR 40 AMPS AT 60 DEGREE TABLE MIN CIRCUIT AMPS 33.5 MAX OVER CURRENT 50 AMPS. NEED 40 AMP BREAKER, 40 AMP FUSE, SEE TABLE LEFT WITH PAPERWORK