Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM01180
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* SMOKE DETECTOR TEST OK |
|
10/27/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. AC-7 FLUE TOO CLOSE TO MAKE UP AIR, VERIFY 60 AMP BREAKER 2. FC-1 PROVIDE SECONDARY DRAIN 3. TAG ALL UNITS 4. PROVIDE DUCT SMOKE DETECTOR TEST WITH AUDIBLE AND VISIBLE ALARMS |
|
10/17/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PROPER DESCRIPTION OF WORK ON PERMIT 2. REVISE PLANS TO REFLECT ALL WORK DONE, INCLUDING CHILLERS, BOILERS, ETC. ALL CHANGE OUTS REQUIRE PERMITS WITH THE EXCEPTION OF EVAP. COOLERS 3. FURTHER INSPECTIONS WITHOUT PROPER PLANS AND PERMITS WILL RESULT IN REFEE's |
|
09/30/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |