Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01180
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/17/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NO WORK PROGRESS |
|
09/30/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CHILLERS: 1. IDENTIFY GROUNDING CONDUCTOR AT CHILLER 2. LABEL DISCONNECTING MEANS 110.22, 110.19 3. BOND JUNCTION BOX ENCLOSURE 250.148 4. NEED PLANS FOR NEW CHILLERS 5. MAINTAIN WORKING CLEARANCES 110.26 CU-1: 1. MAINTAIN WORKING CLEARANCES 2. LABEL DISCONNECT ROOF: 1. LABEL DISCONNECTS 2. PLEASE RE-TIGHTEN ALUMINUM CONNECTIONS 3. MAINTAIN WORKING CLEARANCES 4. FILL UNUSED OPENINGS 5. NEED PLANS FOR WORK & LOADS UNITS: 1. PLAN NOT REFLECTIVE OF WORK INSTALLED |