Permit: T08CM01180

Parcel: 12501026D


Addresses:

2323 E 10TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/28/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/17/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO WORK PROGRESS
09/30/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CHILLERS:
1. IDENTIFY GROUNDING CONDUCTOR AT CHILLER
2. LABEL DISCONNECTING MEANS 110.22, 110.19
3. BOND JUNCTION BOX ENCLOSURE 250.148
4. NEED PLANS FOR NEW CHILLERS
5. MAINTAIN WORKING CLEARANCES 110.26

CU-1:
1. MAINTAIN WORKING CLEARANCES
2. LABEL DISCONNECT

ROOF:
1. LABEL DISCONNECTS
2. PLEASE RE-TIGHTEN ALUMINUM CONNECTIONS
3. MAINTAIN WORKING CLEARANCES
4. FILL UNUSED OPENINGS
5. NEED PLANS FOR WORK & LOADS

UNITS:
1. PLAN NOT REFLECTIVE OF WORK INSTALLED