Permit: T08CM01176

Parcel: 13316030E

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM01176

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
06/11/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SOME JOINTS IN DUCT BOARD STILL LEAKING
06/03/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. ALL DUCT PENETRATIONS THROUGH A FIRE-RATED WALL REQUIRES A FIRE DAMPER
2. REPAIR LEAKING JOINTS IN EXISTING DUCT BOARD
3. IS ROOM 109 INTENDED TO BE FIRE RATED?
4. PROVIDE DIRECTION FROM ENGINEER OR ARCHITECT