Permit: T08CM01176

Parcel: 13316030E

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/05/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
06/19/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- EJECTOR PUMP UNDER SINK SHALL BE SHOWN ON
APPROVED PLAN
- EJECTOR REQUIRES AN ALARM ALSO, CHECK VALVE AND GATE VALVE
- PROVIDE A DETAIL FOR INSTALLATION
- ALSO, CORRECT USE OF FITTINGS REQUIRED
- SANITARY TEES AND CLEANOUT TEES ARE TO BE INSTALLED VERTICALLY AND DON'T LINK WATER FLEXES TOGETHER.