Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01168
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDS AND NEUTRALS TO BE SEPERATE IN TRANSFER SWITCH 2) ALL CONDUCTORS OF FEEDER TO BE ROUTED TOGETHER. THIS INCLUDES EQUIPMENT GROUND. NEEDS TO BE ROUGHTED THRU SAME PINCHED KNOCKOUT IN PANEL 3) OPEN WIRING COMPARTMENT IN GENERATOR 4) OPEN 50 KVA TRANSFORMER FOR INSPECTION |
|
| 04/06/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WORK NEEDS TO BE 100% COMPLETE 2. ALL EQUIPMENT TO BE OPEN FOR INSPECTION 3. PLANS TO BE REVISED TO REFLECT ACTUAL FIELD INSTALLATION |