Permit: T08CM01168

Parcel: 13101002L


Addresses:

2400 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01168

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/21/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/15/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDS AND NEUTRALS TO BE SEPERATE IN TRANSFER SWITCH
2) ALL CONDUCTORS OF FEEDER TO BE ROUTED TOGETHER. THIS INCLUDES EQUIPMENT GROUND. NEEDS TO BE ROUGHTED THRU SAME PINCHED KNOCKOUT IN PANEL
3) OPEN WIRING COMPARTMENT IN GENERATOR
4) OPEN 50 KVA TRANSFORMER FOR INSPECTION
04/06/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WORK NEEDS TO BE 100% COMPLETE
2. ALL EQUIPMENT TO BE OPEN FOR INSPECTION
3. PLANS TO BE REVISED TO REFLECT ACTUAL FIELD INSTALLATION