Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01163
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2010 | ELECTRIC - FINAL | Partial Approval | ||
04/01/2010 | ELECTRIC - FINAL | Approved | PER PH CALL | |
03/17/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/16/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED LETTER FOR SERVICE DISCONNECT CHANGE |
|
03/12/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/11/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND J-BOX CT CAN PER 250 NEC 2) RACEWAY TO HAVE BOND BUSHING PER 250 NEC |
|
02/17/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FEEDERS NOT TERMINATED IN CT YET 2) OK INSIDE BLDG |
|
01/29/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR TO INSTALL UFER NOT SHOWN ON PLAN 2) LETTER FROM ARCHITECT TO ADDRESS THIS AND 800 AMP SES DISCONNECT SWITCH 3) CONTRACTOR WILL TRY TO FIND NOTES FROM UNDER SLAB INSPECTIONS ON OTHER (MALL) PERMIT |
|
01/28/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) 800 AMP SWITCH FOR SES NOT INSTALLED PER E001 PLANS 2) PROVIDE VERIFICATION OF UNDERSLAB INSPECTIONS AND APPROVALS FOR HOMERUN AND BRANC CIRCUITING, INSIDE BLDG COMPLETE CONDUIT RUNS UP COLUMNS 3) A/C HOMERUNS NOT COMPLETE PER PLAN 4) NO UFER INSTALLED (REQUIRED BY CODE FOR NEW CONSTRUCTION) |