Permit: T08CM01149

Parcel: 141354030


Addresses:

10798 E DEEP SKY DR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T08CM01149

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/02/2008 FRAMING Approved IVRS - Inspection :*
07/01/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ANCHORS STILL NEEDED AT STAIRWAY SHEARWALL
2) FRAMING STILL NEEDED BEHIND TUBS 2ND FLOOR
3) PLUMBING NOT FULL
06/30/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SCREW ANCHORS NEEDED AT SHEARWALL UNDER STAIRS PER PLAN
2) OVERNOTCHED STUDS BEARING 2 X 4 WALL BETWEEN GARAGE AND FOYER
3) NAIL OFF SIDES OF SHEAR PANEL BOXES WITH 4-10D NAILS PER 508 DETAIL GARAGE PERIMETER
4) DRAFT STOP SEALED AT TOP OF CHASES AND FLOOR TRUSSES
5) DRAFT STOP TUBS FROM 2ND FLOOR
6) SEAL BOX FOR LOW VOLTAGE WEST SIDE OF GARAGE
7) FRAMING BEHIND UPSTAIRS TUBS
8) NAIL PROTECT ROMEX ABOVE WATER HEATER AT TOP PLATE
9) NAILL PROTECT ROMEX UNDER WINDOW IN DINING ROOM
10) FILL 2ND FLOOR PLUMBING
11) BLOCK MECHANICAL DUCT 2ND FLOOR