Permit: T08CM01129

Parcel: 13355231A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/22/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
08/18/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/15/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. 1/2" DUCT LINER NOT ADEQUATE
2. PROVIDE MIN. R4.2 INSULATION ON ALL DUCTING ABOVE THE CEILING AS PER CITY OF TUCSON AMENDMENTS
3. PROVIDE A LETTER FROM ENGINEER IF CHANGING ANY DETAILS
4. SEAL ALL DUCT JOINTS
07/29/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CONDENSATE PIPE IN WALL OK TO COVER
07/25/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUPPLY & EXHAUST IN RESTROOMS OK TO SHEETROCK RESTROOMS - CONDENSATE DRAIN MUST BE
MIN. 1" DIAMETER
07/24/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*