Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
| 08/18/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/15/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. 1/2" DUCT LINER NOT ADEQUATE 2. PROVIDE MIN. R4.2 INSULATION ON ALL DUCTING ABOVE THE CEILING AS PER CITY OF TUCSON AMENDMENTS 3. PROVIDE A LETTER FROM ENGINEER IF CHANGING ANY DETAILS 4. SEAL ALL DUCT JOINTS |
|
| 07/29/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CONDENSATE PIPE IN WALL OK TO COVER |
|
| 07/25/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPLY & EXHAUST IN RESTROOMS OK TO SHEETROCK RESTROOMS - CONDENSATE DRAIN MUST BE MIN. 1" DIAMETER |
|
| 07/24/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |