Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM01129
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/18/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DROP SEISMIC FOR EXIT FIXTURES IN GRID 300 NEC 2. COMPLETE MAKE UP IN J-BOXES, GROUND ALL J-BOXES 3. MC CABLE TO BE SUPPORTED WITHIN 12" OF TERM. & 6' INTERVALS PER NEC 330.30, 6' OR LESS FOR FIXTURES EXEMPT 4. DO NOT BUNDLE CABLES FOR MORE THAN 2' PER NEC 300.15 |
|
07/17/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK WALLS 2. OK HARD LIDS AND SOFFITS |