Permit: T08CM01129

Parcel: 13355231A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM01129

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/20/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/18/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DROP SEISMIC FOR EXIT FIXTURES IN GRID 300 NEC
2. COMPLETE MAKE UP IN J-BOXES, GROUND ALL J-BOXES
3. MC CABLE TO BE SUPPORTED WITHIN 12" OF TERM. & 6' INTERVALS PER NEC 330.30, 6' OR LESS FOR FIXTURES EXEMPT
4. DO NOT BUNDLE CABLES FOR MORE THAN 2' PER NEC 300.15
07/17/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK WALLS
2. OK HARD LIDS AND SOFFITS