Permit: T08CM01111

Parcel: 11615190K

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T08CM01111

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/13/2009 MECHANICAL - INTERMEDIATE Approved
10/06/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ROCK SOFFIT IN NURSE CALL #2
10/02/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ROCK ISO ROOMS 2 LAYERS
NO COMBUSTIBLE MATERIALS IN PLENUMS
NEED INSULATION IN CURBS
ITEMS 9, 14, 17 -- STILL IN QUESTION
09/17/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
- NO ROCK IN ISOLATION ROOM RESTROOMS OK
- SOFFITS ALL PATIENT ROOMS OK FOR ROCK
- PROVIDE PICTURES OF INSULATION IN ROOF CURBS AT
HP UNITS
- PROVIDE CLARIFICATION FROM ENGINEER ON MECH.
SPECS ITEM 9, 14, 17
- HP-3 NOT PER PLANS, REVISE DUCT SYSTEM TO MATCH DRAWINGS.