Permit: T08CM01111

Parcel: 11615190K

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01111

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/27/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/20/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
INTERIOR ITEMS DONE
WAITING ON ORDER ROOF UNIT
01/14/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ROOMS EXCEPT BATHROOM DEVICES
1. FINISH PANELS
2. ROOF
01/13/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK COX PVC CONDUITS ACROSS ROOF AND UNDERGROUND
01/12/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK HALLWAY & EM LIGHTS IN HALLWAY
01/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF:
1. VERIFY LISTING FOR EXHAUST FAN BLOWER
2. EXPOSED PVC TO BE SCH80 ABOVE GRADE PER CITY AMENDMENTS
3. UNCOVER BURIED PVC CONDUIT TO INSPECT
4. USE SUPPORT THAT WILL SUPPORT CONDUIT
01/07/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
2. EXCESSIVE PAINT ON DEVICE TERMINALS
3. PATIENT CARE RECEPTACLES TO
BE "HOSPITAL GRADE" - 517.18(B)
4. GROUND FIXTURE HARDWARE
5. NEED PANEL BOARD BONDING PER 517.14