Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01111
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/20/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* INTERIOR ITEMS DONE WAITING ON ORDER ROOF UNIT |
|
| 01/14/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ROOMS EXCEPT BATHROOM DEVICES 1. FINISH PANELS 2. ROOF |
|
| 01/13/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK COX PVC CONDUITS ACROSS ROOF AND UNDERGROUND |
|
| 01/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK HALLWAY & EM LIGHTS IN HALLWAY |
|
| 01/09/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1. VERIFY LISTING FOR EXHAUST FAN BLOWER 2. EXPOSED PVC TO BE SCH80 ABOVE GRADE PER CITY AMENDMENTS 3. UNCOVER BURIED PVC CONDUIT TO INSPECT 4. USE SUPPORT THAT WILL SUPPORT CONDUIT |
|