Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01076
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CORRECTIONS NOT COMPLETE TIM @ 602-510-9119 |
|
04/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH SUPPORTING CONDUIT IN CEILING 2. PLANS NOT REFLECTIVE OF WORK INSTALLED 3. FINISH INSTALLING RECEPTACLE SCREWS IN INDUSTRIAL COVER 4. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 5. REAR EXIT TO BE ON AREA SERVED (700.12) 6. TRACK LIGHT TO BE MOVED UPON STORE (OLD) RELOCATION RECEIVED CHECK #7243 FOR $150.00 |