Permit: T08CM01067

Parcel: 124040010


Addresses:

1448 E 1ST ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM01067

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
SUBJECT TO HEALTH DEPT PLAN
07/09/2008 PLUMBING - INTERMEDIATE Not ready for Inspection 1. VENTING BELOW FLOOD RIM, HORIZONTALLY LIMITED TO STRUCTURAL CONDITIONS
2. OK TO INSULATE HOT
3. NEED TO SEE TEST ON ABS
4. GAS OK
07/03/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN, IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE, DOWNSTREAM OF THE TRAP BEING SERVED. EACH VENT SHALL RISE VERTICALLY, TO A POINT NOT LESS THAN 6" ABOVE THE OVERFLOW BEFORE OFFSETTING HORIZONTALLY ALL VENT FITTINGS INSTALLED BELOW FLOOD RIM TO BE DRAINAGE TYPE (SWEEPS AND COMBOS)

ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN 4' BETWEEN HANGERS.
06/26/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*