Inspection Status: Approved
Inspection History: PLUMBING - PRE SLAB
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2008 | PLUMBING - PRE SLAB | Approved | IVRS - Inspection :* INLET, OUTLET, VENT AND SEWER FOR INTERCEPTOR OK TEST OK OK TO COVER |
|
| 07/17/2008 | PLUMBING - PRE SLAB | Not ready for Inspection | IVRS - Inspection :* REVISED APPROVED PLAN ON SITE APPROVED HEALTH DEPT PLAN ON SITE MAY NOT INTERMINGLE ABS/PVC NO TRACER WIRE ON BLDG. SEWER |
|
| 06/26/2008 | PLUMBING - PRE SLAB | Partial Approval | IVRS - Inspection :* 1. INSTALL AVB's ON ALL HOSE BIBS 2. GAS PIPING FOR KITCHEN LINE TO ABOVE CEILING AT ANSUL LOCATION OK TO COVER 3. 1/2" FILTERED WATER PIPING IN SAME WALL OK TO COVER |