Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T08CM01065
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO ROCK UPSTAIRS |
|
| 07/07/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE R-8 INSULATION ON ATTIC DUCT 2. LINE SETS NOT PROPERLY INSULATED 3. EXHAUST FAN T-TOPS NOT BIRD SCREENED 4. PROVIDE 1X RADIUS ON FLEX DUCT BENDS 5. ENCLOSE RETURN PLENUMS DOWNSTAIRS UNITS OK TO ROCK MECHANICAL ONLY |