Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01065
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BRACE AC DISCONNECTS ON ROOF - FALLING OVER 2. BAD GFI RECEPT IN KITCHEN COUNTER #30 BY SINK OK AFTER HRS. INSP. OWNER PAID $150.00 (CK#1227) |
|
09/03/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. AIR HANDLER WIRING - SHEATH ARMOR BROKEN AN EXPOSED CONDUCTORS CHECK WITH MECHANICAL INSPECTOR 2. USE APPROVED HARDWARE WITH DEVICES - NOT DRYWALL SCREWS 3. USE APPROVED COVERS - WOOD PANELING 4. FINISH PREVIOUS ITEMS 2, 4, 7 & CHECK ROOF NEXT TIME 5. KITCHEN RECEPTACLES TO BE GFCI 210.8 |
|
08/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORIES TO BE AS PER 408.4 - NO ABBREVIATION, ALL BREAKERS 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.2 3. FINISH MAKE UP OF AIR HANDLER 4. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS AND RE-TIGHTEN ALUMINUM TERMINATIONS 5. TIGHTEN LOOSE FITTINGS AT WATER HEATER 6. A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER 7. USE TERMINAL ENDS WITH STRANDED CONDUCTORS 8. BATH LIGHT TO BE MADE UP IN BOX NOT FIXTURE 9. GROUND HOOD AND USE SPLICE CONNECTORS PARTIAL INSPECTION - ONE UNIT ONLY |