Permit: T08CM01065

Parcel: 12217284A

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01065

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
09/05/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BRACE AC DISCONNECTS ON ROOF - FALLING OVER
2. BAD GFI RECEPT IN KITCHEN COUNTER #30 BY SINK

OK AFTER HRS. INSP. OWNER PAID $150.00 (CK#1227)
09/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. AIR HANDLER WIRING - SHEATH ARMOR BROKEN AN EXPOSED CONDUCTORS CHECK WITH MECHANICAL INSPECTOR
2. USE APPROVED HARDWARE WITH DEVICES -
NOT DRYWALL SCREWS
3. USE APPROVED COVERS - WOOD PANELING
4. FINISH PREVIOUS ITEMS 2, 4, 7 & CHECK ROOF NEXT TIME
5. KITCHEN RECEPTACLES TO BE GFCI 210.8
08/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL DIRECTORIES TO BE AS PER 408.4 -
NO ABBREVIATION, ALL BREAKERS
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.2
3. FINISH MAKE UP OF AIR HANDLER
4. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS AND RE-TIGHTEN ALUMINUM TERMINATIONS
5. TIGHTEN LOOSE FITTINGS AT WATER HEATER
6. A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER
7. USE TERMINAL ENDS WITH STRANDED CONDUCTORS
8. BATH LIGHT TO BE MADE UP IN BOX NOT FIXTURE
9. GROUND HOOD AND USE SPLICE CONNECTORS

PARTIAL INSPECTION - ONE UNIT ONLY