Permit: T08CM01065

Parcel: 12217284A

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01065

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
08/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WIRING AND OR FLEX PULLED OUT OF CONNECTORS AT AIR HANDLERS IN HALLWAY
2) POWER CHECK POWER TO FINAL INSPECTION
08/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. REPAIR OR REPLACE MAIN BREAKER COVER MISSING ON SERVICE EQUIP. FILL IN HOLES AT MAIN BREAKERS ALL UNITS
2. INSTALL FIXTURES OR CAP OFF ALL WIRING PRIOR TO POWER RELEASE
07/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH ELECTRIC
07/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FINISH STRAPPING NM CABLES AS DISCUSSED
2. CABLES TO ENTER 1/4" OF SHEATHING INTO BOXES
07/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SEE NOTES PREVIOUS INSPECTIONS
2. ALSO, BOXES OVERFILLED - SEE 314.16
3. SUPPORT ROMEX PER CODE SEE 334 NEC
4. OK 1ST FLOOR CEILING ONLY
07/03/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BLUE WIRE NUTS CANNOT ACCOMODATE 3 #6 CONDUCTORS
CONDUCTOR PULLED OUT WHEN MOVED
2. GROUND LIGHT SWITCHES
3. USE PROPER SPLICING HARDWARE WHEN SPLICING ALUM WITH COPPER PROVIDE LETTER FOR BLUE WIRE NUTS
4. BE SURE TO PIGTAIL GROUNDS FOR DEVICES CORRECTLY
5. ROMEX CONNECTORS OVER FILLED
07/02/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
07/01/2008 ELECTRIC - INTERMEDIATE Denied AS PREVIOUSLY REQUESTED-SUBMIT A LETTER BY ELECTRICAL CONTRACTOR STATING THAT THEY ARE RESPONSIBLE FOR ANY NEW, REPLACED, ADDED OR REMODELED WORK UNDER THIS PERMIT AND ASSUMES ALL RESPONSIBILITY FOR ALL ELECTRICAL WORK, AND THAT THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE FOR ALL ELECTRICAL WORK. CALLED RON GALLUS AND JASON FLOOD TO ADVISE OF THIS TODAY
06/30/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PREVIOUS CORRECTIONS NOT COMPLETED
06/24/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1. FINISH STAPLING & SUPPORTING NM CABLES AS PER CODE
2. FINISH MAKE UP
3. PLEASE VERIFY BOX FILL

INSPECTOR WILL NOT MAKE A PUNCH LIST
06/20/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
ELECTRICAL CONTRACTOR TO BE ON SITE AND
NAME PUT ON PERMIT
06/19/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/18/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY - CHECK SAME ALL UNITS

UNIT 32
1. MAX 15 AMP ON 14GA WIRING
2. SELF TAP SCREW
3. NEED SERVICE RECEPTACLES FOR ALL AC UNITS

UNIT 31
1. NEED SQ D BREAKERS
06/16/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
ELECTRICAL CONTRACTOR (LEADING EDGE) ELECTRIC IS IN THE PROCESS OF GOING THROUGH ALL UNITS
06/11/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED A LICENSED ELECTRICAL CONTRACTOR FOR ALL WORK
2. THE CONTRACTOR IS TO PROVIDE COMPANY LETTERHEAD THAT SAYS WIRING HAS BEEN INSPECTED AND REPLACED AS NEEDED
3. NAIL PLATES ARE REQUIRED WHERE HOLE IS LESS
THAN 1 1/4" FROM STUD FACE
4. SMOKE DETECTORS ARE REQUIRED TO BE INTER-CONNECTED
5. PAINTED OVER DEVICES WILL NEED REPLACEMENT
FOR FINAL
6. WIRING NOT PER PLAN

PARTIAL INSPECTION ONLY

ELECTRICAL CONTRACTOR TO GO THROUGH UNITS AND MAKE SURE PER PLAN/CODE

ELECTRICAL CONTRACTOR TO BE ON SITE NEXT INSPECTION