Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM01065
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WIRING AND OR FLEX PULLED OUT OF CONNECTORS AT AIR HANDLERS IN HALLWAY 2) POWER CHECK POWER TO FINAL INSPECTION |
|
08/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. REPAIR OR REPLACE MAIN BREAKER COVER MISSING ON SERVICE EQUIP. FILL IN HOLES AT MAIN BREAKERS ALL UNITS 2. INSTALL FIXTURES OR CAP OFF ALL WIRING PRIOR TO POWER RELEASE |
|
07/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH ELECTRIC |
|
07/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. FINISH STRAPPING NM CABLES AS DISCUSSED 2. CABLES TO ENTER 1/4" OF SHEATHING INTO BOXES |
|
07/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SEE NOTES PREVIOUS INSPECTIONS 2. ALSO, BOXES OVERFILLED - SEE 314.16 3. SUPPORT ROMEX PER CODE SEE 334 NEC 4. OK 1ST FLOOR CEILING ONLY |
|
07/03/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BLUE WIRE NUTS CANNOT ACCOMODATE 3 #6 CONDUCTORS CONDUCTOR PULLED OUT WHEN MOVED 2. GROUND LIGHT SWITCHES 3. USE PROPER SPLICING HARDWARE WHEN SPLICING ALUM WITH COPPER PROVIDE LETTER FOR BLUE WIRE NUTS 4. BE SURE TO PIGTAIL GROUNDS FOR DEVICES CORRECTLY 5. ROMEX CONNECTORS OVER FILLED |
|
07/02/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
07/01/2008 | ELECTRIC - INTERMEDIATE | Denied | AS PREVIOUSLY REQUESTED-SUBMIT A LETTER BY ELECTRICAL CONTRACTOR STATING THAT THEY ARE RESPONSIBLE FOR ANY NEW, REPLACED, ADDED OR REMODELED WORK UNDER THIS PERMIT AND ASSUMES ALL RESPONSIBILITY FOR ALL ELECTRICAL WORK, AND THAT THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE FOR ALL ELECTRICAL WORK. CALLED RON GALLUS AND JASON FLOOD TO ADVISE OF THIS TODAY | |
06/30/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PREVIOUS CORRECTIONS NOT COMPLETED |
|
06/24/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1. FINISH STAPLING & SUPPORTING NM CABLES AS PER CODE 2. FINISH MAKE UP 3. PLEASE VERIFY BOX FILL INSPECTOR WILL NOT MAKE A PUNCH LIST |
|
06/20/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* ELECTRICAL CONTRACTOR TO BE ON SITE AND NAME PUT ON PERMIT |
|
06/19/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/18/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY - CHECK SAME ALL UNITS UNIT 32 1. MAX 15 AMP ON 14GA WIRING 2. SELF TAP SCREW 3. NEED SERVICE RECEPTACLES FOR ALL AC UNITS UNIT 31 1. NEED SQ D BREAKERS |
|
06/16/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* ELECTRICAL CONTRACTOR (LEADING EDGE) ELECTRIC IS IN THE PROCESS OF GOING THROUGH ALL UNITS |
|
06/11/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED A LICENSED ELECTRICAL CONTRACTOR FOR ALL WORK 2. THE CONTRACTOR IS TO PROVIDE COMPANY LETTERHEAD THAT SAYS WIRING HAS BEEN INSPECTED AND REPLACED AS NEEDED 3. NAIL PLATES ARE REQUIRED WHERE HOLE IS LESS THAN 1 1/4" FROM STUD FACE 4. SMOKE DETECTORS ARE REQUIRED TO BE INTER-CONNECTED 5. PAINTED OVER DEVICES WILL NEED REPLACEMENT FOR FINAL 6. WIRING NOT PER PLAN PARTIAL INSPECTION ONLY ELECTRICAL CONTRACTOR TO GO THROUGH UNITS AND MAKE SURE PER PLAN/CODE ELECTRICAL CONTRACTOR TO BE ON SITE NEXT INSPECTION |