Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08CM01061
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2009 | FIRE - FINAL | Approved | ||
12/24/2008 | FIRE - FINAL | Partial Approval | 1st half Add sprinkler coverage in IT room head over 10' off wall. 2nd half Add sprinkler coverage in hallway by office supply storage room, head over 11' off wall. Lower heads in clean room below ceciling and just outside of clean room room door. Womens bathroom correct sprinkler head by north door add chorme escutcheon to keep head center in hole. |
|
10/13/2008 | FIRE - FINAL | Partial Approval | Temp C of O approved. Sprinkler heads shall be 1" below drop ceiling for proper operation, this will stop final C of O if all heads are not adjusted when final is called in. | |
10/06/2008 | FIRE - FINAL | Denied | Correct sprinkler heads in break room Correct sprinkler coverage in IT room Correct sprinkler head in mens restroom Correct sprinkler heads thoughout remodel area heads to far up ceciling tiles. Have sprinkler contractor call in on his permit. |