Permit: T08CM01061

Parcel: 14029003H

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T08CM01061

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2009 FIRE - FINAL Approved
12/24/2008 FIRE - FINAL Partial Approval 1st half
Add sprinkler coverage in IT room head over 10' off wall.
2nd half
Add sprinkler coverage in hallway by office supply storage room, head over 11' off wall.
Lower heads in clean room below ceciling and just outside of clean room room door.
Womens bathroom correct sprinkler head by north door add chorme escutcheon to keep head center in hole.
10/13/2008 FIRE - FINAL Partial Approval Temp C of O approved. Sprinkler heads shall be 1" below drop ceiling for proper operation, this will stop final C of O if all heads are not adjusted when final is called in.
10/06/2008 FIRE - FINAL Denied Correct sprinkler heads in break room
Correct sprinkler coverage in IT room
Correct sprinkler head in mens restroom
Correct sprinkler heads thoughout remodel area heads to far up ceciling tiles.
Have sprinkler contractor call in on his permit.